Physical and chemical parameters 19/01/2018 09:30 18/01/2018 09:30 17/01/2018 09:30 16/01/2018 09:30 15/01/2018 09:30 Unit VMR VMA
Chloride   13.3 12.9 13.1 13.8 13.5 mg/L 25 250*
Sodium   -- -- -- -- -- mg/L 20 150
Potassium   -- -- -- -- -- mg/L 10 12
Magnesium   -- -- -- -- -- mg/L 30 50
Calcium   -- -- -- -- -- mg/L 100 -
Free chlorine   0.74 0.79 0.82 0.83 0.79 mg/L - -
pH value   7.6 8.0 7.5 7.5 7.8 pH unit 6.5-8.5 6.5-9.5
Fluoride   -- -- -- -- 0.16 mg/L 0.6 1.7
Total hardness   -- -- -- -- -- mg/L CaCO3 - 500
Remarks   According to Decree-Law No. 46/96/M
<< RADARM >>
All data is subject to IACM final report
Remarks: VMR - Recommended maximum value
VMA - Acceptable maximum value
* EU 98/83/EC parametric value
Fluoride test (1/week);Sodium, potassium, magnesium, calcium and total hardness test (1/month, 1/week at salinity period)